Undersized transformers overheat and fail early. Oversized units waste capital and run at poor efficiency. This guide walks through a defensible sizing procedure aligned with IEEE C57.12.00 and IEC 60076.
Step 1 — Connected vs. Demand Load
Multiply connected load by demand factor (typ. 0.6-0.9 for commercial, 0.4-0.7 for residential). Apply diversity factor across feeders (1.1-1.5).
Step 2 — Include Harmonic K-Factor
For loads with VFDs, UPS, and LED drivers, choose K-13 or K-20 transformers. Ignoring harmonics forces derating up to 30%.